TRANSDUCER FOR AC CURRENT


The transducer converts an AC current into a load independent DC current or voltage signal which may be used to drive a number of remotely installed instruments.

The measuring principle is "arithmetic mean calibrated to RMS sinusoidal" and this transducer is therefore only suitable for undistorted sine wave measurements.

The normal response time is suitable for indicating instruments and recorders. A lower ripple - slower response version for data loggers can be supplied.

The output is protected against over-voltages due to surges or accidental contact with insulation testers or the mains supply.

The auxiliary voltage supply is user selectable to either 110V or 220V AC by means of a jumper. Similarly the input range may be changed to either 0-1A or 0-5A.

MODE OF OPERATION

The current to be measured is transformed in and converted in the active rectifier(3). The auxiliary supply is transformed in PT (2), rectified and smoothed in (4) and is used to power the rectifier (3), output amplifier (5) and to provide the offset voltage for the live zero version. The output amplifier (5) provides either a load independent current (with maximum burden) or a load independent voltage (with minimum burden) signal.

Block Diagram

CONNECTION DIAGRAM

Connection Diagram
DIN A Housing


LDG 10 Housing


/
Technical Details
1. Input  
Input quantity: User selectable
0 - 1 A or 0 - 5 A
Frequency: 45 - 55 - 65 Hz
Consumption burden: 0.3VA at rated input
Overload in terms of rated input: 1.2x indefinitely
40x 0.5 seconds
2. Output  
Characteristic: A or C or D
Output quantity: Impressed current signal (voltage signal on request)
Standard values: 1mA, 5mA, 20mA
Maximum load: 5k, 2.5k, 750 Ohm
Maximum output voltage: 32V DC
Maximum output current: 1.25x rated (typical)
2.0x rated (maximum)
Ripple: 0.5% standard
Response time: 210ms standard
3. Auxiliary power supply  
Voltage: User selectable
110 or 220V 50Hz
Burden: <3.5VA at rated output
4. Accuracy  
Error limit at rated conditions: ±0.5% of range at 23°C and 45-55 Hz sinusoidal wave, form factor 1.11
Linearity error: 0.05%
Long term drift: 0.25%
Temperature shift: 400ppm/°C
Variation with auxiliary supply: 0.05% for ±20% variation
5. Protection  
Impulse test between isolated sets of terminals: 5kV (0.5J 1.2/50 wave) IEC standard
Voltage withstand rating between sets of terminals: 4kV, 50Hz AC for 1 minute
Power voltage across output: 220V, 50Hz indefinitely
Surge across output terminals: 5kV 25J
1kV 4J
6. Physical constraints  
Working temperature: -25 to 13 to 33 to 55°C
Storage temperature: -55 to 75°C (above dewpoint)
Relative humidity: 80%
Variation due to external magnetic field (worst case): 0.05% at 400A/m 50Hz
Position: Surface mounting in any position indoors.
7. Enclosure DIN A
LDG10