TRANSDUCERS FOR AC CURRENT AND VOLTAGE


The transducer converts an AC current or voltage into a load independent DC current or voltage signal which may be used to drive a number of remotely installed instruments.

The measuring principle is "arithmetic mean calibrated to RMS sinusoidal" and this transducer is therefore only suitable for undistorted sine wave measurements.

The normal response time is suitable for indicating instruments and recorders. A lower ripple - slower response version for data loggers can be supplied.

The output is protected against over-voltages due to surges or accidental contact with insulation testers.

Internal jumpers allow selecting either 110V or 220V AC auxiliary supply.

MODE OF OPERATION

The current/voltage to be measured is transformed in (1) and converted in the active rectifier(3). The auxiliary supply is transformed in PT(2), rectified and smoothed in (4) and is used to power the rectifier (3), output amplifier (5) and to provide the offset voltage for the live zero version. The output amplifier (5) provides either a load independent current (with maximum burden) or a load independent voltage (with minimum burden) signal.

Block Diagram

CONNECTION DIAGRAM

Connection Diagram
LDG6 Housing


Overload in terms of rated input:
Technical Data
1. Input  
Input quantity: 0 - 1 A or 0 - 5 A
0 - 120 / 250 / 500 / 600V. Other values on request.
Frequency: 45 - 55 - 65 Hz
Consumption burden: 0.3VA at rated input
Overload in terms of rated input  1.2x indefinitely
Current:40x 0.5 seconds
Voltage: 2x 10 seconds
2. Output  
Characteristic: Live zero
Output quantity: Impressed current signal
Standard value: 0 - 20mA or 4 - 20mA
Maximum load: 500 Ohm
Maximum output current: 1.25x rated (typical)
2.0x rated (maximum)
Ripple: 0.5% standard
Response time: 210ms standard
3. Auxiliary power supply  
110V or 220V AC 50 Hz  
4. Accuracy  
Error limit at rated conditions: ±0.5% of range at 23°C and 45-55 Hz sinusoidal wave, form factor 1.11
Linearity error: 0.05%
Long term drift: 0.25%
Temperature shift: 400ppm/°C
Variation with auxiliary supply: 0.05% for ±20% variation
5. Protection  
Impulse test between isolated sets of terminals: 5kV (0.5J 1.2/50 wave) IEC standard
Voltage withstand rating between sets of terminals: 4kV, 50Hz AC for 1 minute
Surge across output terminals: 25J 1 x 8/20 micro seconds
6. Physical constraints  
Working temperature: -25 to 13 to 33 to 55°C
Storage temperature: -55 to 75°C (above dewpoint)
Relative humidity: 80%
Variation due to external magnetic field (worst case): 0.05% at 400A/m 50Hz
Position: Surface mounting in any position indoors.
7. Enclosure LDG6